Section 8
1MAC050144-MB C
Measurement functions
538
615 series ANSI
Technical Manual
Figure 294:
Integral deadband supervision
The deadband value used in the integral calculation is configured with the
X deadband
setting. The value represents the percentage of the difference between the maximum and
minimum limit in the units of 0.001 percent * seconds.
The reporting delay of the integral algorithms in seconds is calculated with the formula:
(Equation 60)
Example for IA, IB, IC:
A deadband = 2500 (2.5% of the total measuring range of 40)
I_INST_A
=
I_DB_A
= 0.30
If
I_INST_A
changes to 0.40, the reporting delay is:
t s
deadband
Y
( )
(max min)
/
%
=
−
×
×
1000
100
Δ
t s
s
( )
(
)
/
.
.
%
=
− ×
−
×
=
40 0
2500 1000
0 40 0 30 100
10