Section 4
1MAC050144-MB C
Protection functions
200
615 series ANSI
Technical Manual
Figure 92:
Functional module diagram. I
1
and I
2
represent positive and negative
phase sequence currents. I_A, I_B and I_C represent phase currents.
I
2
/I
1
The I
2
/I
1
module calculates the ratio of the negative and positive phase sequence current.
It reports the calculated value to the level detector.
Level detector
The level detector compares the calculated ratio of negative and positive phase sequence
currents with the set
Pickup value
. If the calculated value exceeds the set
Pickup value
and
the min current check module has exceeded the minimum phase current limit, the level
detector reports the exceeding of the value to the timer.
Min current check
The min current check module checks whether the measured phase currents are above the
set
Min phase current
. At least one of the phase currents needs to be above the set limit to
enable the level detector module.
Timer
Once activated, the timer activates the
PICKUP
output. The time characteristic is
according to DT. When the trip timer has reached the value set by
Trip delay time
, the
TRIP
output is activated. If the fault disappears before the module trips, the reset timer is
activated. If the reset timer reaches the value set by
Reset delay time
, the trip timer resets
and the
PICKUP
output is deactivated.
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the ratio
of the pickup situation and the set trip time. The value is available through the Monitored
data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting
"Configuration/System/
Blocking
mode
"
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......