Section 11
1MAC050144-MB C
General function block features
650
615 series ANSI
Technical Manual
11.2.1.2
User-programmable inverse-time characteristics
The user can define curves by entering parameters into the following standard formula:
(Equation 80)
t[s] Trip time (in seconds)
A
set
Curve parameter A
B
set
Curve parameter B
C
set
Curve parameter C
E
set
Curve parameter E
I
Measured current
I>
set
Pickup value
k
set
Time multiplier
11.2.1.3
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is a
ground-fault specific characteristic.
The RI-type is calculated using the formula
(Equation 81)
The RD-type is calculated using the formula
(Equation 82)
t[s]
Trip time (in seconds)
k
set
Time multiplier
I
Measured current
I>set
Pickup value
t s
k
I
I
[ ]
.
.
=
−
× >
⎛
⎝
⎜
⎜
⎜⎜
⎞
⎠
⎟
⎟
⎟⎟
0 339 0 236
t s
I
k I
[ ]
.
.
=
−
×
× >
⎛
⎝⎜
⎞
⎠⎟
5 8 1 35 In
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......