Section 4
1MAC050144-MB C
Protection functions
136
615 series ANSI
Technical Manual
Table 118: Measurement modes supported by 67/51P and 67/50P stages
4.1.3.6
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area is
limited with the
Min forward angle
and
Max forward angle
settings. The reverse operation
area is limited with the
Min reverse angle
and
Max reverse angle
settings.
In the forward operation area, the
Max forward angle
setting gives the counterclockwise
sector and the
Min forward angle
setting gives the corresponding clockwise sector,
measured from the
Characteristic angle
setting.
In the backward operation area, the
Max reverse angle
setting gives the counterclockwise
sector and the
Min reverse angle
setting gives the corresponding clockwise sector, a
measurement from the
Characteristic angle
setting that has been rotated 180 degrees.
Relay characteristic angle (RCA) is set positive if the operating current lags the polarizing
quantity and negative if the operating current leads the polarizing quantity.
Measurement mode
Supported measurement modes
67/51P and 67/50P-1
67/50P-2
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
The sector limits are always given as positive degree values.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......