Figure 272:
Simplified CBB initiation diagram
INIT_1... 6
initiation lines
CBB1...CBB2
first two cycle building blocks
The operation of a CBB consists of two parts: initiation and execution. In the initiation
part, the status of the initiation lines is compared to the CBB settings. In order to allow the
initiation at any of the initiation line activation, the corresponding switch in the
Init signals
CBB_
parameter must be set to TRUE. In order to block the initiation, the corresponding
switch in the
Blk signals CBB_
parameter must be set to TRUE.
If any of the initiation lines set with the
Init signals CBB_
parameter is active and no
initiation line causes blocking, the CBB requests for execution.