Section 11
1MAC050144-MB C
General function block features
674
615 series ANSI
Technical Manual
11.3.2.2
User-programmable inverse-time characteristics for undervoltage
protection
The user can define curves by entering parameters into the standard formula:
(Equation 88)
t[s]
trip time in seconds
A
the set value of
Curve parameter A
B
the set value of
Curve parameter B
C
the set value of
Curve parameter C
D
the set value of
Curve parameter D
E
the set value of
Curve parameter E
V
measured voltage
V<
the set value of
Pickup value
k
the set value of
Time multiplier
11.3.2.3
IDMT curve saturation of undervoltage protection
For the undervoltage IDMT mode of operation, the integration of the trip time does not
start until the voltage falls below the value of
Pickup value
. To cope with discontinuity
characteristics of the curve, a specific parameter for saturating the equation to a fixed value
is created. The
Curve Sat Relative
setting is the parameter and it is given in percents
compared with
Pickup value
. For example, due to the curve equation B, the characteristics
equation output is saturated in such a way that when input voltages are in the range from
Pickup value
to
Curve Sat Relative
in percents under
Pickup value
, the equation uses
Pickup value
* (1.0 -
Curve Sat Relative
/ 100 ) for the measured voltage. Although, the
curve A has no discontinuities when the ratio V/V> exceeds the unity,
Curve Sat Relative
is set for it as well. The
Curve Sat Relative
setting for curves A, B and C is 2.0 percent.
However, it should be noted that the user must carefully calculate the curve characteristics
concerning also discontinuities in the curve when the programmable curve equation is
used. Thus, the
Curve Sat Relative
parameter gives another degree of freedom to move the
inverse curve on the voltage ratio axis and it effectively sets the maximum trip time for the
IDMT curve because for the voltage ratio values affecting by this setting, the operation
time is fixed, that is, the definite time, depending on the parameters but no longer the
voltage.
11.4
Measurement modes
In many current or voltage dependent function blocks, there are four alternative measuring
principles:
• RMS
• DFT which is a numerically calculated fundamental component of the signal
• Peak-to-peak
t s
k A
B
V
V
V
C
D
E
⎡
⎣⎢
⎤
⎦⎥
=
⋅
× < −
<
−
⎛
⎝⎜
⎞
⎠⎟
+
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......