3.3
LED indication control
The IED includes a global conditioning function LEDPTRC that is used with the
protection indication LEDs.
LED indication control is preconfigured in a such way that all the protection functions
general pickup and trip signals are combined with this function (available as output signals
OUT_PICKUP
and
OUT_TRIP
). These signals are always internally connected to Pickup
and Trip LEDs. LEDPTRC collects and combines phase information from different
protection functions (available as output signals
OUT_PU_A /_B /_C
and
OUT_TRP_A
/_B /_C
). There is also combined ground fault information collected from all the ground
fault functions available in the IED configuration (available as output signals
OUT_PU_NEUT
and
OUT_TRP_NEUT
).
3.4
Time synchronization
The IED has an internal real-time clock which can be either free-running or synchronized
from an external source. The real-time clock is used for time stamping events, recorded
data and disturbance recordings.
The IED is provided with a 48-hour capacitor back-up that enables the real-time clock to
keep time in case of an auxiliary power failure.
Setting
Synch Source
determines the method how the real-time clock is synchronized. If
set to “None”, the clock is free-running and the settings
Date
and
Time
can be used to set
the time manually. Other setting values activate a communication protocol that provides
the time synchronization. Only one synchronization method can be active at a time but
SNTP provides time master redundancy.
The IED supports SNTP, IRIG-B, DNP3 and Modbus to update the real-time clock.
IRIG-B with GPS provides the best accuracy.
LED indication control should never be used for tripping purposes. There
is a separate trip logic function TRPPTRC available in the IED
configuration.
When Modbus TCP or DNP3 over TCP/IP is used, SNTP time
synchronization should be used for better synchronization accuracy.
DNP3 can be used as a time synchronization source.
When the SNTP server IP setting is changed, the IED must be rebooted to
activate the new IP address. The SNTP server IP settings are normally
defined in the engineering phase via the SCL file.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......