1MAC050144-MB C
Section 5
Protection related functions
615 series ANSI
383
Technical Manual
Section 5
Protection related functions
5.1
Three-phase transformer inrush detector INR
5.1.1
Identification
5.1.2
Function block
Figure 184:
Function block
5.1.3
Functionality
The transformer inrush detection INR is used to coordinate transformer inrush situations
in distribution networks.
Transformer inrush detection is based on the following principle: the output signal
BLK2H
is activated once the numerically derived ratio of second harmonic current I_2H and the
fundamental frequency current I_1H exceeds the set value.
The trip time characteristic for the function is of definite time (DT) type.
The function contains a blocking functionality. Blocking deactivates all outputs and resets
timers.
5.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of an inrush current detection function can be described by using a module
diagram. All the blocks in the diagram are explained in the next sections.
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase inrush detector
INRPHAR
3I2f>
INR
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......