Section 6
Supervision functions
615 series ANSI
453
Technical Manual
6.4.8
Monitored data
Table 390: MCS 3I, I2 Monitored data
6.5
Fuse failure supervision 60
6.5.1
Identification
6.5.2
Function block
Figure 241:
Function block
6.5.3
Functionality
The fuse failure supervision function SEQRFUF is used to block the voltage measuring
functions at a failure in the secondary circuits between the voltage transformer and IED to
avoid misoperations of the voltage protection functions.
SEQRFUF has two algorithms, a negative sequence-based algorithm and a delta current
and delta voltage algorithm.
A criterion based on the delta current and the delta voltage measurements can be activated
to detect three-phase fuse failures which usually are more associated with the voltage
transformer switching during station operations.
Name
Type
Values (Range)
Unit
Description
INT_BLKD
BOOLEAN
0=False
1=True
Function blocked internally
MCS 3I, I2
Enum
1=on
Status
2=blocked
3=test
4=test/blocked
5=off
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision
SEQRFUF
FUSEF
60
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......