Section 6
1MAC050144-MB C
Supervision functions
444
615 series ANSI
Technical Manual
Figure 236:
Connection diagram for current circuit supervision with two sets of
three-phase current transformer protection cores
When using the measurement core for reference current measurement, it
should be noted that the saturation level of the measurement core is much
lower than with the protection core. This should be taken into account
when setting the current circuit supervision function.