1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
347
Technical Manual
saturation at external faults. When the operation of the restrained low stage is blocked by
the second harmonic blocking functionality, the BLKD2H output is activated.
When operation of the restrained differential is blocked by the fifth harmonic blocking
functionality, the BLKD5H output is activated. Correspondingly, when the operation of
the restrained differential is blocked by the waveform blocking functionality, the
BLKDWAV output is activated according to the phase information.
When required, the trip outputs of the restrained low stage can be blocked by the
BLK_OPR_LS or BLOCK external control signals
.
Figure 166:
Operation characteristic for restrained operation of 87T
The Low trip value of the restrained differential function is determined according to the
operation characteristic:
Low trip value
= Id1
Slope section 2
is determined correspondingly:
(Equation 41)
The second turning point
End section 2
can be set in the range of 100 percent to 500
percent.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......