Section 11
1MAC050144-MB C
General function block features
636
615 series ANSI
Technical Manual
(Equation 78)
t[s]
t[s] = Trip time in seconds
I
measured current
I>
set
Pickup value
k
set
Time multiplier
Table 540: Curve parameters for ANSI and IEC IDMT curves
Curve name
A
B
C
(1) ANSI Extremely Inverse
28.2
0.1217
2.0
(2) ANSI Very Inverse
19.61
0.491
2.0
(3) ANSI Normal Inverse
0.0086
0.0185
0.02
(4) ANSI Moderately Inverse
0.0515
0.1140
0.02
(6) Long Time Extremely Inverse
64.07
0.250
2.0
(7) Long Time Very Inverse
28.55
0.712
2.0
(8) Long Time Inverse
0.086
0.185
0.02
(9) IEC Normal Inverse
0.14
0.0
0.02
(10) IEC Very Inverse
13.5
0.0
1.0
(11) IEC Inverse
0.14
0.0
0.02
(12) IEC Extremely Inverse
80.0
0.0
2.0
(13) IEC Short Time Inverse
0.05
0.0
0.04
(14) IEC Long Time Inverse
120
0.0
1.0
The maximum guaranteed measured current is 50 x In for the current
protection. When the set
Pickup value
exceeds 1.00 x In, the turn point
where the theoretical IDMT characteristics are leveling out to the definite
time can be calculated with the formula:
(Equation 79)
t s
A
I
I
B k
c
[ ]
=
>
⎛
⎝⎜
⎞
⎠⎟
−
+
⎛
⎝
⎜
⎜
⎜
⎜⎜
⎞
⎠
⎟
⎟
⎟
⎟⎟
⋅
1
Turn point
Pickupvalue
=
50
×
In
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......