circuit breakers the factor y is normally 2. In case of a high-voltage system, the factor y
can be 1.4...1.5.
Remaining life of the breaker
Every time the breaker operates, the life of the circuit breaker reduces due to wearing. The
wearing in the breaker depends on the tripping current, and the remaining life of the
breaker is estimated from the circuit breaker trip curve provided by the manufacturer.
Example for estimating the remaining life of a circuit breaker
Figure 222:
Trip Curves for a typical 12 kV, 630 A, 16 kA vacuum interrupter
Nr
the number of closing-opening operations allowed for the circuit breaker
Ia
the current at the time of tripping of the circuit breaker
Calculation of Directional Coef
The directional coefficient is calculated according to the formula: