Section 4
1MAC050144-MB C
Protection functions
272
615 series ANSI
Technical Manual
Figure 128:
Load-shedding operation in the “Freq< AND df/dt>” mode when both
Freq< and df/dt conditions are satisfied (Rated frequency=50 Hz)
60 Hz
Pickup value Freq
set at 0.975 xFn
Pickup value df/dt
set at -0.020 xFn/s
Trip Tm df/dt
= 500ms
Trip Tm Freq
= 1000ms
Load shed mode
= Freq< AND df/dt
58.8 Hz
ST_FRG
OPR_FRG
500ms
1s
TRIP is activated as
Freq< AND df/dt
condition satisfied
TRIP
58.5 Hz
Start of operation timer
ST_FRQ
OPR_FRQ
Start of operation timer
1s
Time [s]
Frequency
[Hz]