Section 3
1MAC050144-MB C
Basic functions
58
615 series ANSI
Technical Manual
For further information on internal fault indications, see the operation manual.
3.2.2
Warnings
In case of a warning, the IED continues to operate except for those protection functions
possibly affected by the fault, and the green Normal LED remains lit as during normal
operation.
Warnings are indicated with the text
Warning
and is additionally provided with the name
of the warning, a numeric code, and the date and time on the LHMI. The fault indication
message can be manually cleared.
If a fault appears, record the name and code so that it can be provided to ABB customer
service.
Internal Fault
Conf. error,X000
62
Card in slot X000 is wrong type.
Internal Fault
Conf. error,X100
63
Card in slot X100 is wrong type or does not
belong to the original composition.
Internal Fault
Conf. error,X110
64
Card in slot X110 is wrong type, is missing, or
does not belong to the original composition.
Internal Fault
Conf. error,X120
65
Card in slot X120 is wrong type, is missing or
does not belong to the original composition.
nternal Fault
Conf. error,X130
66
Card in slot X130 is wrong type, is missing or
does not belong to the original composition.
Internal Fault
Card error,X000
72
Card in slot X000 is faulty.
Internal Fault
Card error,X100
73
Card in slot X100 is faulty.
Internal Fault
Card error,X110
74
Card in slot X110 is faulty.
Internal Fault
Card error,X120
75
Card in slot X120 is faulty.
Internal Fault
Card error,X130
76
Card in slot X130 is faulty.
Internal Fault
LHMI module
79
LHMI module is faulty. The fault indication may
not be seen on the LHMI during the fault.
Internal Fault
RAM error
80
Error in the RAM memory on the CPU card.
Internal Fault
ROM error
81
Error in the ROM memory on the CPU card.
Internal Fault
EEPROM error
82
Error in the EEPROM memory on the CPU card.
Internal Fault
FPGA error
83
Error in the FPGA on the CPU card.
Internal Fault
RTC error
84
Error in the RTC on the CPU card.
Internal Fault
RTD card error, X130
96
Card in slot X130 has RTD fault.
Fault indication
Fault code
Additional information
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...