Section 6
1MAC050144-MB C
Supervision functions
456
615 series ANSI
Technical Manual
Table 391: Fuse failure output control
The activation of the
BLOCK
input deactivates both
FUSEF_U
and
FUSEF_3PH
outputs.
6.5.5
Application
Some protection functions operate on the basis of the measured voltage value in the IED
point. These functions can fail if there is a fault in the measuring circuits between the
voltage transformers and the IED.
A fault in the voltage measuring circuit is referred to as a fuse failure. This term is
misleading since a blown fuse is just one of the many possible reasons for a broken circuit.
Fuse-failure detection criterion
Conditions and function response
Negative phase sequence criterion
If a fuse failure is detected based on the negative
phase-sequence criterion, the
FUSEF_U
output is
activated.
If the fuse-failure detection is active for more than
five seconds and at the same time all the phase
voltage values are below the set value of the
Seal in
voltage
setting with
Enable seal in
turned to "Yes",
the function activates the
FUSE_3PH
output signal.
The
FUSEF_U
output signal is also activated if all the
phase voltages are above the
Seal in voltage
setting
for more than 60 seconds and at the same time the
negative sequence voltage is above
Neg Seq
voltage Lev
for more than 5 seconds, all the phase
currents are below the
Current dead Lin Val
setting
and the circuit breaker is closed, that is,
CB_CLOSED
is TRUE.
Current and voltage delta function criterion
If the current and voltage delta criterion detects a
fuse failure condition, but all the voltages are not
below the
Seal in voltage
setting, only the
FUSEF_U
output is activated.
If the fuse-failure detection is active for more than
five seconds and at the same time all the phase
voltage values are below the set value of the
Seal in
voltage
setting with
Enable seal in
turned to "Yes",
the function activates the
FUSE_3PH
output signal.
External fuse-failure detection
The
MINCB_OPEN
input signal is supposed to be
connected through an IED binary input to the N.C.
auxiliary contact of the miniature circuit breaker
protecting the VT secondary circuit.
The
MINCB_OPEN
signal sets the
FUSEF_U
output
signal to block all the voltage-related functions when
MCB is in the open state.
The
DISCON_OPEN
input signal is supposed to be
connected through an IED binary input to the N.C.
auxiliary contact of the line disconnector. The
DISCON_OPEN
signal sets the
FUSEF_U
output
signal to block the voltage-related functions when
the line disconnector is in the open state.
It is recommended to always set
Enable seal in
to "Yes". This secures that
the blocked protection functions remain blocked until normal voltage
conditions are restored if the fuse-failure has been active for 5 seconds, that
is, the fuse failure outputs are deactivated when the normal voltage
conditions are restored.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......