Section 5
1MAC050144-MB C
Protection related functions
386
615 series ANSI
Technical Manual
5.1.6
Signals
Table 334: INR Input signals
Table 335: INR Output signals
5.1.7
Settings
Table 336: INR Group settings
Table 337: INR Non group settings
5.1.8
Monitored data
Table 338: INR Monitored data
Name
Type
Default
Description
I_2H_A
SIGNAL
0
Second harmonic phase A current
I_1H_A
SIGNAL
0
Fundamental frequency phase A current
I_2H_B
SIGNAL
0
Second harmonic phase B current
I_1H_B
SIGNAL
0
Fundamental frequency phase B current
I_2H_C
SIGNAL
0
Second harmonic phase C current
I_1H_C
SIGNAL
0
Fundamental frequency phase C current
BLOCK
BOOLEAN
0=False
Block input status
Name
Type
Description
BLK2H
BOOLEAN
Second harmonic based block
Parameter
Values (Range)
Unit
Step
Default
Description
PIckup value
5...100
%
1
20
Ratio of the 2. to the 1. harmonic leading to restraint
Operate delay time
20...60000
ms
1
20
Operate delay time
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Off / On
Reset delay time
0...60000
ms
1
20
Reset delay time
Name
Type
Values (Range)
Unit
Description
INR
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......