Section 4
1MAC050144-MB C
Protection functions
278
615 series ANSI
Technical Manual
4.3.2.6
Signals
Table 273: 81LS H input signals
Table 274: 81SH output signals
Name
Type
Default
Description
F
SIGNAL
0
Measured frequency
dF/dt
SIGNAL
0
Rate of change of frequency
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
BLK_REST
BOOLEAN
0=False
Block restore
MAN_RESTORE
BOOLEAN
0=False
Manual restore signal
Name
Type
Description
TRIP
BOOLEAN
Trip of load shedding
OPR_FRQ
BOOLEAN
Trip signal for under frequency
OPR_FRG
BOOLEAN
Trip signal for high df/dt
PICKUP
BOOLEAN
Pickup
ST_FRQ
BOOLEAN
Pick-Up signal for under frequency detection
ST_FRG
BOOLEAN
Pick-Up signal for high df/dt detection
RESTORE
BOOLEAN
Restore signal for load restoring purposes
ST_REST
BOOLEAN
Restore frequency attained and restore timer started
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......