1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
305
Technical Manual
4.5.2.8
Monitored data
Table 304: 49T Monitored data
4.5.2.9
Technical data
Table 305: 49T Technical data
4.5.3
Thermal overload protection for motors, 49M
4.5.3.1
Identification
Name
Type
Values (Range)
Unit Description
TEMP
FLOAT32
-100.0...9999.9
°C
The calculated temperature of the protected
object
TEMP_RL
FLOAT32
0.00...99.99
The calculated temperature of the protected
object relative to the operate level
T_TRIP
INT32
0...60000
s
Estimated time to operate in seconds
T_ENA_CLOSE
INT32
0...60000
s
Estimated time to deactivate InhRec in seconds
TEMP_AMB
FLOAT32
-99...999
°C
The ambient temperature used in the
calculation
49T
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Characteristic
Value
Pickup accuracy
Depending on the frequency of the current
measured: f
n
±2Hz
Current measurement: ±1.5% of the set value or
±0.002 x I
n
(at currents in the range of 0.01...4.00 x
I
n
)
Trip time accuracy
1
1. Overload current > 1.2 x Trip level temperature
±2.0% of the theoretical value or ±0.50 s
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase thermal overload protection
for motors
MPTTR
3Ith>M
49M
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......