Section 11
1MAC050144-MB C
General function block features
632
615 series ANSI
Technical Manual
Figure 337:
Operating effect of the
BLOCK
input when the selected blocking mode is
"Freeze timer"
If the
BLOCK
input is activated when the trip timer is running, as described in Figure 337,
the timer is frozen during the time
BLOCK
remains active. If the timer input is not active
longer than specified by the
Reset delay time
setting, the trip timer is reset in the same way
as described in Figure 335, regardless of the
BLOCK
input.
The selected blocking mode is "Freeze timer".