1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
209
Technical Manual
Table 196: 46M Non group settings
4.1.9.9
Monitored data
Table 197: 46M Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Rated current
0.30...2.00
xIn
0.01
1.00
Rated current (Ir) of the machine (used only in the IDMT)
Maximum trip time
500000...7200000
ms
1000
1000000
Max trip time regardless of the inverse characteristic
Minimum trip time
100...120000
ms
1
100
Minimum trip time for IDMT curves
Cooling time
5...7200
s
1
50
Time required to cool the machine
Reset delay time
0...60000
ms
1
20
Reset delay time
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
T_ENARESTART
FLOAT32
0.00...7200.00
s
Estimated time to reset of block restart
46M
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......