1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
115
Technical Manual
Transformer and busbar overcurrent protection with reverse blocking
principle
By implementing a full set of overcurrent protection stages and blocking channels between
the protection stages of the incoming feeders, bus-tie and outgoing feeders, it is possible
to speed up the operation of overcurrent protection in the busbar and transformer LV-side
faults without impairing the selectivity. Also, the security degree of busbar protection is
increased, because there is now a dedicated, selective and fast busbar protection
functionality which is based on the blockable overcurrent protection principle. The
additional time selective stages on the transformer HV and LV-sides provide increased
security of backup protection for the transformer, busbar and also for the outgoing feeders.
Depending on the overcurrent stage in question, the selectivity of the scheme in Figure 47
is based on the operating current, operating time or blockings between successive
overcurrent stages. With blocking channels, the operating time of the protection can be
drastically shortened if compared to the simple time selective protection. In addition to the
busbar protection, this blocking principle is applicable for the protection of transformer
LV terminals and short lines. The functionality and performance of the proposed
overcurrent protections can be summarized as seen in the table.
Table 90:
Proposed functionality of numerical transformer and busbar overcurrent protection. DT = definite
time, IDMT = inverse definite minimum time
In case the bus-tie breaker is open, the operating time of the blockable overcurrent
protection is approximately 100 ms (relaying time). When the bus-tie breaker is closed,
that is, the fault current flows to the faulted section of the busbar from two directions, the
operation time becomes as follows: first the bus-tie relay unit trips the tie breaker in the
above 100 ms, which reduces the fault current to a half. After this the incoming feeder
relay unit of the faulted bus section trips the breaker in approximately 250 ms (relaying
time), which becomes the total fault clearing time in this case.
O/C-stage
Operating char.
Selectivity mode
Operation speed
Sensitivity
HV/51P
DT/IDMT
time selective
low
very high
HV/50P-1/2
DT
blockable/time
selective
high/low
high
HV/50P-3
DT
current selective
very high
low
LV/51P
DT/IDMT
time selective
low
very high
LV/50P-1/2
DT
time selective
low
high
LV/50P-3
DT
blockable
high
high
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......