Section 3
1MAC050144-MB C
Basic functions
98
615 series ANSI
Technical Manual
active longer than the set Cold load time, also the output remains active until the input is
deactivated
Settings
Table 77:
PT Non group settings
Figure 37:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
Parameter
Values (Range)
Unit
Step
Default
Description
Pulse delay time 1
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 2
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 3
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 4
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 5
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 6
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 7
0...3600000
ms
10
0
Pulse delay time
Pulse delay time 8
0...3600000
ms
10
0
Pulse delay time
IN#
OUT#
t
A
B
to
to +
Cold load
time
t1
t1 +
Cold load time
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......