Section 4
1MAC050144-MB C
Protection functions
142
615 series ANSI
Technical Manual
Figure 62:
Phasors in a single-phase ground fault, phases A-N, and two-phase
short circuit, phases B and C, when the actuating polarizing quantity is
the negative-sequence voltage -V2
Positive-sequence voltage as polarizing quantity
Table 123: Equations for calculating angle difference for positive-sequence quantity polarizing method
Faulted
phases
Used fault
current
Used
polarizing
voltage
Angle difference
A
I
A
V1
B
I
B
V1
C
I
C
V1
A - B
I
A
- I
B
V1
B - C
I
B
- I
C
V1
C - A
I
C
- I
A
V1
ANGLE A
V
I
A
RCA
_
( )
(
)
=
−
−
1
ANGLE B
V
I
B
RCA
_
( )
(
)
=
−
−
−
1
120
ANGLE C
V
I
C
RCA
_
( )
(
)
=
−
−
+
1
120
ANGLE A
V
I
I
A
B
RCA
_
( )
(
)
=
−
−
−
+
1
30
ANGLE B
V
I
I
B
C
RCA
_
( )
(
)
=
−
−
−
−
1
90
ANGLE C
V
I
I
C
A
RCA
_
( )
(
)
=
−
−
−
+
1
150
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......