1MAC050144-MB C
Section 6
Supervision functions
615 series ANSI
429
Technical Manual
6.1.7
Settings
Table 374: 52CM Non group settings
Parameter
Values (Range)
Unit Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Acc stop current
5.00...500.00
A
0.01
10.00
RMS current setting below which engy acm stops
Open alarm time
0...200
ms
1
40
Alarm level setting for open travel time in ms
Close alarm time
0...200
ms
1
40
Alarm level Setting for close travel time in ms
Opening time Cor
0...100
ms
1
10
Correction factor for open travel time in ms
Closing time Cor
0...100
ms
1
10
Correction factor for CB close travel time in ms
Spring charge time
0...60000
ms
10
1000
Setting of alarm for spring charging time of CB in ms
Counter initial Val
0...9999
1
0
The operation numbers counter initialization value
Alarm Op number
0...9999
1
200
Alarm limit for number of operations
Lockout Op number
0...9999
1
300
Lock out limit for number of operations
Current exponent
0.00...2.00
0.01
2.00
Current exponent setting for energy calculation
Difference Cor time
-10...10
ms
1
5
Corr. factor for time dif in aux. and main contacts open time
Alm Acc currents Pwr
0.00...20000.00
0.01
2500.00
Setting of alarm level for accumulated currents power
LO Acc currents Pwr
0.00...20000.00
0.01
2500.00
Lockout limit setting for accumulated currents power
Ini Acc currents Pwr
0.00...20000.00
0.01
0.00
Initial value for accumulation energy (Iyt)
Directional Coef
-3.00...-0.50
0.01
-1.50
Directional coefficient for CB life calculation
Operation cycle
0...9999
1
5000
Operation cycle at rated current
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating current of the breaker
Rated fault current
500.00...75000.00
A
0.01
5000.00
Rated fault current of the breaker
Op number rated
1...99999
1
10000
Number of operations possible at rated current
Op number fault
1...10000
1
1000
Number of operations possible at rated fault current
Life alarm level
0...99999
1
500
Alarm level for CB remaining life
Pressure alarm time
0...60000
ms
1
10
Time delay for gas pressure alarm in ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas pressure lockout in ms
Inactive Alm days
0...9999
1
2000
Alarm limit value of the inactive days counter
Ini inactive days
0...9999
1
0
Initial value of the inactive days counter
Inactive Alm hours
0...23
h
1
0
Alarm time of the inactive days counter in hours
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......