Timer 2
Once activated, the timer runs until the set
CB failure delay
value is elapsed. The time
characteristic is according to DT. When the operation timer has reached the set maximum
time value
CB failure delay
, the
TRBU
output is activated. The value of this setting is made
as low as possible at the same time as any unwanted operation is avoided. A typical setting
is 90 - 150 ms which is also dependent on the retrip timer.
The minimum time delay for the retrip can be estimated as:
(Equation 49)
t
cbopen
maximum opening time for the circuit breaker
t
BFP_reset
is the maximum time for the breaker failure protection to detect the correct breaker function (the
current criteria reset)
t
margin
safety margin
It is often required that the total fault clearance time is less than the given critical time. This
time is often dependent on the ability to maintain transient stability in case of a fault close
to a power plant.
Figure 191:
Time line of breaker failure protection
Timer 3
This module is activated by the
CB_FAULT
signal. Once activated, the timer runs until the
set
CB fault delay
value is elapsed. The time characteristic is according to DT. When the
operation timer has reached the maximum time value, the
CB_FAULT_AL
output is
activated. After the set time an alarm is given so that actions can be done to repair the
circuit breaker. A typical value is 5 s.
CBfailuredelay Retriptime t
t
t
cbopen
BFP reset
margin
≥
+
+
+
_
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......