Section 7
1MAC050144-MB C
Control functions
512
615 series ANSI
Technical Manual
7.2.8
Settings
Table 426: 79 Non group settings
Parameter
Values (Range)
Unit
Step Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Off/On
Reclosing operation
1=Off
2=External Ctl
3=On
1=Off
Reclosing operation (Off, External Ctl / On)
Manual close mode
0=False
1=True
0=False
Manual close mode
Wait close time
50...10000
ms
50
250
Allowed CB closing time after reclose command
Max wait time
100...1800000
ms
100
10000
Maximum wait time for haltDeadTime release
Max trip time
100...10000
ms
100
10000
Maximum wait time for deactivation of protection
signals
Close pulse time
10...10000
ms
10
200
CB close pulse time
Max Thm block time
100...1800000
ms
100
10000
Maximum wait time for thermal blocking signal
deactivation
Cut-out time
0...1800000
ms
100
10000
Cutout time for protection coordination
Reclaim time
100...1800000
ms
100
10000
Reclaim time
Dsr time shot 1
0...10000
ms
100
0
Discrimination time for first reclosing
Dsr time shot 2
0...10000
ms
100
0
Discrimination time for second reclosing
Dsr time shot 3
0...10000
ms
100
0
Discrimination time for third reclosing
Dsr time shot 4
0...10000
ms
100
0
Discrimination time for fourth reclosing
Terminal priority
1=None
2=Low (follower)
3=High (master)
1=None
Terminal priority
Synchronisation set
0...127
0
Selection for synchronizing requirement for
reclosing
Auto wait time
0...60000
ms
10
2000
Wait time for reclosing condition fullfilling
Auto lockout reset
0=False
1=True
1=True
Automatic lockout reset
Protection crd limit
1...5
1
Protection coordination shot limit
Protection crd mode
1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
4=AR inop, CB man
Protection coordination mode
Auto initiation cnd
1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
2=When sync fails
Auto initiation condition
Tripping line
0...63
0
Tripping line, defines INIT inputs which cause
OPEN_CB activation
Control line
0...63
63
Control line, defines INIT inputs which are
protection signals
Enable shot jump
0=False
1=True
1=True
Enable shot jumping
CB closed Pos status
0=False
1=True
1=True
Circuit breaker closed position status
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......