Section 4
1MAC050144-MB C
Protection functions
232
615 series ANSI
Technical Manual
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects the
phase or phases in which the fault level is detected. If the number of faulty phases match
with the set
Num of pickup phases
, the phase selection logic activates the timer.
Timer
Once activated, the timer activates the
PICKUP
output. Depending on the value of the set
Operating curve type
, the time characteristics are selected according to DT or IDMT.
When the operation timer has reached the value set by
Trip delay time
in the DT mode or
the maximum value defined by the IDMT, the
TRIP
output is activated.
When the user-programmable IDMT curve is selected, the trip time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation occurs, that is, a fault suddenly disappears before the trip delay is
exceeded, the reset state is activated. The behavior in the drop-off situation depends on the
selected trip time characteristics. If the DT characteristics are selected, the reset timer runs
until the set
Reset delay time
value is exceeded. If the drop-off situation exceeds the set
Reset delay time
, the timer is reset and the
PICKUP
output is deactivated.
When the IDMT trip time curve is selected, the functionality of the timer in the drop-off
state depends on the combination of the
Type of reset curve
and
Reset delay time
settings.
Table 229: The reset time functionality when the IDMT trip time curve is selected
For a detailed description of the voltage IDMT curves, see the General
function block features section in this manual.
Type of reset curve
Description of operation
“Immediate”
The trip timer is reset instantaneously when drop-off
occurs
“Def time reset”
The trip timer is frozen during drop-off. The trip timer
is reset after the set
Reset delay time
is exceeded
“DT Lin decr rst”
The trip timer value linearly decreases during the
drop-off situation. The trip timer is reset after the set
Reset delay time
is exceeded
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......