Section 8
1MAC050144-MB C
Measurement functions
546
615 series ANSI
Technical Manual
8.2.0.4
Settings
Table 450: IA,IB,IC Non group settings
Parameter
Values (Range) Unit Step Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Off / On
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required by limit supervision
Demand interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
0=1 minute
Time interval for demand calculation
A high high limit
0.00...40.00
xIn
1.40
High alarm current limit
A high limit
0.00...40.00
xIn
1.20
High warning current limit
A low limit
0.00...40.00
xIn
0.00
Low warning current limit
A low low limit
0.00...40.00
xIn
0.00
Low alarm current limit
A deadband
100...100000
2500
Deadband configuration value for integral calculation. (percentage of
difference between min and max as 0,001 % s)
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......