Table 20:
DNP3: Non group settings
CtlStructPWd2
****
Password for Modbus control
struct 2
CtlStructPWd3
****
Password for Modbus control
struct 3
CtlStructPWd4
****
Password for Modbus control
struct 4
CtlStructPWd5
****
Password for Modbus control
struct 5
CtlStructPWd6
****
Password for Modbus control
struct 6
CtlStructPWd7
****
Password for Modbus control
struct 7
CtlStructPWd8
****
Password for Modbus control
struct 8
Parameter
Values (Range)
Unit
Step Default
Description
DNP physical layer
1=Serial
2=TCP/IP
2=TCP/IP
DNP physical layer
Unit address
1...65519
1
1
DNP unit address
Master address
1...65519
1
3
DNP master and UR address
Serial port
0=Not in use
1=COM 1
2=COM 2
0=Not in use
COM port for serial interface, when physical layer is serial.
Need time interval
0...65535
min
1
30
Period to set IIN need time bit
Time format
0=UTC
1=Local
1=Local
UTC or local. Coordinate with master.
CROB select timeout
1...65535
sec
1
10
Control Relay Output Block select timeout
Data link confirm
0=Never
1=Only Multiframe
2=Always
0=Never
Data link confirm mode
Data link confirm TO
100...65535
ms
1
3000
Data link confirm timeout
Data link retries
0...65535
1
3
Data link retries count
Data link Rx to Tx delay
0...255
ms
1
0
Turnaround transmission delay
Data link inter char delay
0...20
char
1
4
Inter character delay for incoming messages
App layer confirm
1=Disable
2=Enable
1=Disable
Application layer confirm mode
App confirm TO
100...65535
ms
1
5000
Application layer confirm and UR timeout
App layer fragment
256...2048
bytes
1
2048
Application layer fragment size
Legacy master SBO
1=Disable
2=Enable
1=Disable
Legacy DNP Master SBO sequence number relax enable
Default Var Obj 01
1...2
1
1
1=BI; 2=BI with status.
Default Var Obj 02
1...2
1
2
1=BI event; 2=BI event with time.
Default Var Obj 30
1...4
1
2
1=32 bit AI; 2=16 bit AI; 3=32 bit AI without flag; 4=16 bit AI
without flag.
Default Var Obj 32
1...4
1
4
1=32 bit AI event; 2=16 bit AI event; 3=32 bit AI event with
time; 4=16 bit AI event with time.
Table continued on next page
Parameter
Values (Range)
Unit
Step
Default
Description
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......