1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
93
Technical Manual
Function block
Figure 27:
Function blocks
Settings
The function does not have any parameters available in LHMI or Protection and Control
IED Manager (PCM600).
3.13.1.2
AND function block
Functionality
AND and AND6 are used to form general combinatory expressions with Boolean
variables.
The default value in all inputs is logical true, which makes it possible to use only the
required number of inputs and leave the rest disconnected.
AND has two inputs and AND6 has six inputs.Function block
Function block
Figure 28:
Function blocks
OR
B1
B2
O
B1
B2
O
B3
B4
B5
B6
OR6
AND
B1
B2
O
B1
B2
O
B3
B4
B5
B6
AND6