Section 5
1MAC050144-MB C
Protection related functions
408
615 series ANSI
Technical Manual
feeder and generates an external trip signal to all IEDs protecting the outgoing feeders,
which in turn results in tripping of all circuit breakers of the outgoing feeders.
Figure 207:
Arc flash detector with several IEDs and a separate arc flash detector
system
5.5.6
Signals
Table 355: AFD Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
I_G
SIGNAL
0
Ground current
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
REM_FLT_ARC
BOOLEAN
0=False
Remote Fault arc detected
OPR_MODE
BOOLEAN
0=False
Operation mode input