1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
277
Technical Manual
Table 270: Setting for a five-step underfrequency operation
The rate of change of frequency function is not instantaneous since the function needs time
to supply a stable value. It is recommended to have a time delay long enough to take care
of the signal noise.
Small industrial systems can experience the rate of change of frequency as large as 5 Hz/s
due to a single event. Even large power systems can form small islands with a large
imbalance between the load and generation when severe faults or combinations of faults
are cleared. Up to 3 Hz/s has been experienced when a small island becomes isolated from
a large system. For normal severe disturbances in large power systems, the rate of change
of the frequency is much less, often just a fraction of 1.0 Hz/s.
Similarly, the setting for df/dt can be from 0.1 Hz/s to 1.2 Hz/s in steps of 0.1 Hz/s to 0.3
Hz/s for large distributed power networks, with the operating time varying from a few
seconds to a few fractions of a second. Here, the operating time should be kept in minimum
for the higher df/dt setting.
Table 271: Setting for a five-step df/dt< operation
Once the frequency has stabilized, the shed load can be restored. The restoring operation
should be done stepwise, taking care that it does not lead the system back to the emergency
condition.
Table 272: Setting for a five-step restoring operation
Load-shedding steps
Pickup value Freq setting
Trip Tm Freq setting
1
0.984 · Fn (59 Hz)
45000 ms
2
0.978 · Fn (58.7 Hz)
30000 ms
3
0.968 · Fn (58.1 Hz)
15000 ms
4
0.958 · Fn (57.5 Hz)
5000ms
5
0.950 · Fn (57 Hz)
500 ms
Load-shedding steps
Pickup value df/dt setting
Trip Tm df/dt setting
1
-0.005 · Fn /s (-0.3 Hz/s)
8000 ms
2
-0.010 · Fn /s (-0.6 Hz/s)
2000 ms
3
-0.015 · Fn /s (-0.9 Hz/s)
1000 ms
4
-0.020 · Fn /s (-1.2 Hz/s)
500 ms
5
-0.025 · Fn /s (-1.5 Hz/s)
250 ms
Load-shedding steps
Restoring pickup Val setting
Restore delay time
setting
1
0.990 · Fn (59.4 Hz)
200000 ms
2
0.990 · Fn (59.4 Hz)
160000 ms
3
0.990 · Fn (59.4 Hz)
100000 ms
4
0.990 · Fn (59.4 Hz)
50000 ms
5
0.990 · Fn (59.4 Hz)
10000 ms
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......