1MAC050144-MB C
Section 8
Measurement functions
615 series ANSI
565
Technical Manual
8.9.4
Settings
Table 481: SP, SE Non group settings
8.9.5
Monitored data
Table 482: SP, SE Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1= enable
5= disable
1=enable
Operation Disable / Enable
Power unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for presentation of the power related
values.
Energy unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for presentation of the energy related
values.
Active power Dir
1=Forward
2=Reverse
1=Forward
Direction of active power flow: Forward, Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward
Direction of reactive power flow: Forward, Reverse
Forward Wh Initial
0...999999999
1
0
Preset Initial value for forward active energy
Reverse Wh Initial
0...999999999
1
0
Preset Initial value for reverse active energy
Forward VArh Initial
0...999999999
1
0
Preset Initial value for forward reactive energy
Reverse VArh Initial
0...999999999
1
0
Preset Initial value for reverse reactive energy
Name
Type
Values (Range)
Unit
Description
SA-kVA
FLOAT32
-999999.9...999999.9
kVA
Apparent power, magnitude of instantaneous value, Phase A
SB-kVA
FLOAT32
-999999.9...999999.9
kVA
Apparent power, magnitude of instantaneous value, Phase B
SC-kVA
FLOAT32
-999999.9...999999.9
kVA
Apparent power, magnitude of instantaneous value, Phase C
PA-kW
FLOAT32
-999999.9...999999.9
kW
Active power, magnitude of instantaneous value, Phase A
PB-kW
FLOAT32
-999999.9...999999.9
kW
Active power, magnitude of instantaneous value, Phase B
PC-kW
FLOAT32
-999999.9...999999.9
kW
Active power, magnitude of instantaneous value, Phase C
QA-kVAr
FLOAT32
-999999.9...999999.9
kVAr
Reactive power, magnitude of instantaneous value, Phase A
QB-kVAr
FLOAT32
-999999.9...999999.9
kVAr
Reactive power, magnitude of instantaneous value, Phase B
QC-kVAr
FLOAT32
-999999.9...999999.9
kVAr
Reactive power, magnitude of instantaneous value, Phase C
PFA
FLOAT32
-1.00…1.00
Power factor, magnitude of instantaneous value, Phase A
PFB
FLOAT32
-1.00…1.00
Power factor, magnitude of instantaneous value, Phase B
PFC
FLOAT32
-1.00…1.00
Power factor, magnitude of instantaneous value, Phase C
Max demand SL1
FLOAT32
-999999.9...999999.9
kVA
Maximum demand for Phase A
Max demand SL2
FLOAT32
-999999.9...999999.9
kVA
Maximum demand for Phase B
Max demand SL3
FLOAT32
-999999.9...999999.9
kVA
Maximum demand for Phase C
Min demand SL1
FLOAT32
-999999.9...999999.9
kVA
Minimum demand for Phase A
Min demand SL2
FLOAT32
-999999.9...999999.9
kVA
Minimum demand for Phase B
Min demand SL3
FLOAT32
-999999.9...999999.9
kVA
Minimum demand for Phase C
Max demand PL1
FLOAT32
-999999.9...999999.9
kW
Maximum demand for Phase A
Max demand PL2
FLOAT32
-999999.9...999999.9
kW
Maximum demand for Phase B
Table continued on next page
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......