Section 4
1MAC050144-MB C
Protection functions
148
615 series ANSI
Technical Manual
Table 129: 67/51P-1 and 67/50P-1 Non group settings
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Voltage Mem time
0...3000
ms
1
40
Voltage memory time
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Characteristic angle
-179...180
deg
1
60
Characteristic angle
Max forward angle
0...90
deg
1
80
Maximum phase angle in forward direction
Max reverse angle
0...90
deg
1
80
Maximum phase angle in reverse direction
Min forward angle
0...90
deg
1
80
Minimum phase angle in forward direction
Min reverse angle
0...90
deg
1
80
Minimum phase angle in reverse direction
Pol quantity
-2=Pos. seq. volt.
1=Self pol
4=Neg. seq. volt.
5=Cross pol
5=Cross pol
Reference quantity used to determine fault direction
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for trip activation
Minimum trip time
20...60000
ms
1
20
Minimum trip time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Curve parameter A
0.0086...120.0000
28.2000
Parameter A for customer programmable curve
Curve parameter B
0.0000...0.7120
0.1217
Parameter B for customer programmable curve
Curve parameter C
0.02...2.00
2.00
Parameter C for customer programmable curve
Curve parameter D
0.46...30.00
29.10
Parameter D for customer programmable curve
Curve parameter E
0.0...1.0
1.0
Parameter E for customer programmable curve
Allow Non Dir
0=False
1=True
0=False
Allows prot activation as non-dir when dir info is invalid
Min trip current
0.01...1.00
xIn
0.01
0.01
Minimum trip current
Min trip voltage
0.01...1.00
xVn
0.01
0.01
Minimum trip voltage
Parameter
Values (Range)
Unit
Step
Default
Description
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......