Section 6
1MAC050144-MB C
Supervision functions
432
615 series ANSI
Technical Manual
The
BLOCK
input can be controlled with a binary input, a horizontal communication input
or an internal signal of the relay program. The activation of the
BLOCK
input prevents the
ALARM
output to be activated.
6.2.5
Application
TCM detects faults in the electrical control circuit of the circuit breaker. The function can
supervise both open and closed coil circuits. This kind of monitoring is necessary to find
out the vitality of the control circuits continuously.
The following figure shows an application of the trip-circuit monitoring function usage.
The best solution is to connect an external R
ext
shunt resistor in parallel with the circuit
breaker internal contact. Although the circuit breaker internal contact is open, TCM can
see the trip circuit through R
ext
. The R
ext
resistor should have such a resistance that the
current through the resistance remains small, that is, it does not harm or overload the
circuit breaker's trip coil.
Figure 225:
Operating principle of the trip-circuit supervision with an external resistor.
The TCM blocking switch is not required since the external resistor is
used.
If the TCM is required only in a closed position, the external shunt resistance may be
omitted. When the circuit breaker is in the open position, the TCM sees the situation as a
faulty circuit. One way to avoid TCM operation in this situation would be to block the
monitoring function whenever the circuit breaker is open.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...