Section 4
1MAC050144-MB C
Protection functions
122
615 series ANSI
Technical Manual
Table 100: 50P-1/2 Non group settings
Table 101: 50P-3 Group settings
Table 102: 50P-3 Non group settings
4.1.1.10
Monitored data
Table 103: 51P Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for trip activation
Minimum trip time
20...60000
ms
1
20
Minimum trip time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Curve parameter A
0.0086...120.0000
28.2000
Parameter A for customer programmable curve
Curve parameter B
0.0000...0.7120
0.1217
Parameter B for customer programmable curve
Curve parameter C
0.02...2.00
2.00
Parameter C for customer programmable curve
Curve parameter D
0.46...30.00
29.10
Parameter D for customer programmable curve
Curve parameter E
0.0...1.0
1.0
Parameter E for customer programmable curve
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
1.00...40.00
xIn
0.01
1.00
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Trip delay time
20...200000
ms
10
20
Trip delay time
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for trip activation
Reset delay time
0...60000
ms
1
20
Reset delay time
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
51P
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......