1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
101
Technical Manual
Figure 41:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
3.13.3
Local/remote control function block CONTROL
3.13.3.1
Function block
Figure 42:
Function block
3.13.3.2
Functionality
Local/Remote control is by default realized through the R/L button on the front panel. The
control via binary input can enabled by setting the value of the
LR control
setting to
"Binary input".
The actual Local/Remote control state is evaluated by the priority scheme on the function
block inputs. If more than one input is active, the input with the highest priority is selected.
The actual state is reflected on the CONTROL function outputs. Only one output is active
at a time.
CONTROL
CTRL_LOC
CTRL_OFF
OFF
LOCAL
CTRL_REM
CTRL_STA
STATION
REMOTE
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......