CEP 6502GU/GTL, 6503GU/GTL 

99577, 99577C 

Temporary branch power distribution unit 

 with Ground Fault Protection for personnel

 

 

 

Installation and Operating Instructions 

 
SPECIFICATION 
These installation and operation instructions 
apply to the following temporary power 
branch distribution system components. Do 
not discard these instructions, save for future 
Reference. 

PORATBLE POWER  

DISTRIBUTION UNITS 

These units are rated 20, 30, or 50 amps, 
125/250 VAC, Single Phase. The max. ampacity 
for these units is 40A @ 120V. The 20 amp, 120 
volt outlets are individually protected by circuit 
breakers and GFCI circuit modules. 
 

Model 

Number(s) 

20 Amp 

Receptacle 

6502GU,6503GU 

99577,99577C 

U-Ground 

6502GTL, 6503GTL 

Twist Lock 

            
INTRODUCTION 
CEP temporary power distribution units equipped 
with GFCI modules that will protect you from 
electrocution hazards resulting from ground 
faults.  Ground faults are current leaks and can 
result in electric shock. Currents of only 60/1000 
of an ampere can be fatal. The GFCI protection 
provided by CEP temporary power distribution 
units significantly minimizes shock hazards. CEP 
temporary power distribution units,  
 

 

 
 

 

which are UL listed as Class A, Group I 
interrupters, respond to fault currents as low as 
3-6 milliamperes, and will shut of the current 
within 1/40

th

 of a second. The temporary power 

distribution unit is designed to provide protection 
against electrical shock hazards due to line-to-
ground faults. Although the GFCI module does 
not eliminate the hazard of a shock, it does limit 
the duration of the shock to a period considered 
safe for normally healthy persons. 
GFCI modules will provide protection against 
ground faults only. They will not protect against 
overloads or short circuits. There is no known 
device that will guard against the electrical shock 
hazard resulting from contact with both the “hot” 
and neutral wires of the electrical circuit. 
ELECTRICITY IS DANGEROUS. 
EVEN WHEN SAFETY DEVICES ARE 
PRESENT, HANDLE WITH CARE AND USE 
REASONABLE CAUTION. 
 
LET CAUTION PREVAIL 
The CEP temporary power distribution unit is 
designed to be used on a grounded electrical 
supply system. It will not operate when supplied 
from a power source which is not grounded.  
Over-current protection of the proper rating, 
according to the National Electric Code, Article 
240, must be used on the supply circuit feeding 
the temporary power distribution units. 
 
 
 
 

 

 