1MAC050144-MB C
Section 7
Control functions
615 series ANSI
523
Technical Manual
Figure 287:
Determination of the alarm limit for a still-active command signal
Closing is permitted during Maximum Syn time, starting from the moment the external
command signal CL_COMMAND is activated. The CL_COMMAND input must be kept
active for the whole time that the closing conditions are waited to be fulfilled. Otherwise,
the procedure is cancelled. If the closing command conditions are fulfilled during
Maximum Syn time, a closing pulse is delivered to the circuit breaker. If the closing
conditions are not fulfilled during the checking time, the alarm CL_FAIL_AL is activated
as an indication of a failed closing attempt. The closing pulse is not delivered if the closing
conditions become valid after Maximum Syn time has elapsed. The closing pulse is
delivered only once for each activated external command signal and new closing
command sequence cannot be started until the external command signal is reset and then
activated again. The SYNC_INPRO output is active when the closing command sequence
is in progress and it is reset when the CL_COMMAND input is reset or Maximum Syn
time has elapsed.
Bypass mode
25 can be set into bypass mode by setting the parameters Synchro check mode and
Energizing check mode to "Off" or alternatively, by activating the BYPASS input.
In bypass mode, the closing conditions are always considered to be fulfilled by the 25
function. Otherwise, the operation is similar to the normal mode.
Voltage angle difference adjustment
In application where the power transformer is located between the voltage measurement
and the vector group connection gives phase difference to the voltages between the high
and low-voltage sides, the angle adjustment can be used to meet synchronism.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......