Section 4
Protection functions
615 series ANSI
281
Technical Manual
Figure 132:
Functional module diagram
Directional detector
The Directional detector module compares the angle of positive sequence current (I
1
) to
the angle of positive sequence voltage (V
1
). Using the positive sequence voltage angle as
the reference the positive sequence current angle is compared to the
Characteristic angle
setting. If the angular difference is within the operating sector selected by the
Directional
mode
setting, then enable signal is sent to the Timer.
The operating sector is defined by the setting
Min forward angle
,
Max forward angle
,
Min
reverse angle
, and
Max reverse angle
(see Figure 133). The user selectable options for
Directional mode
settings are “Forward” and “Reverse”
The sector limits are always given as positive degree values.
The
Characteristic angle
is also known as Relay Characteristic Angle
(RCA), Relay Base Angle or Maximum Torque Line.
Directional
detector
V1
I1
BLOCK
RELEASE
Blocking
logic
t
Timer
Low level
blocking
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......