1MAC050144-MB C
Section 5
Protection related functions
615 series ANSI
395
Technical Manual
5.3
Protection trip conditioning 86/94
5.3.1
Identification
5.3.2
Function block
Figure 193:
Function block
5.3.3
Functionality
The protection trip conditioning function 86/94 is intended to be used as a trip command
collector and handler after the protection functions. The features of this function influence
the trip signal behavior of the circuit breaker. The user can set the minimum trip pulse
length when the non-latched mode is selected. It is also possible to select the latched or
lockout mode for the trip signal.
5.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of a trip logic function can be described by using a module diagram. All the
blocks in the diagram are explained in the next sections:
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Protection trip conditioning
TRPPTRC
Master Trip
86/94
When the 86/94 function is disabled, all trip outputs which are intended to
go through the function to the circuit breaker trip coil are blocked!
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......