Section 3
1MAC050144-MB C
Basic functions
50
615 series ANSI
Technical Manual
Table 21:
COM1/COM2 serial communication settings
Parameter
Values (Range)
Unit
Step
Default
Description
Fiber mode
0=No fiber
2=Fiber optic
0=No fiber
Fiber mode for COM1
Serial mode
1=RS485 2Wire
2=RS485 4Wire
3=RS232 no handshake
4=RS232 with handshake
1=RS485 2Wire
Serial mode for COM1
CTS delay
0...60000
0
CTS delay for COM1
RTS delay
0...60000
0
RTS delay for COM1
Baudrate
1=300
2=600
3=1200
4=2400
5=4800
6=9600
7=19200
8=38400
9=57600
10=115200
6=9600
Baudrate for COM1
Parity
0=None
1=old
2=even
2=even
Parity for COM1
If this protocol does not operate as expected, check that another serial
protocol is not using the same COM port.
DNP 3.0 protocol ignores any parity setting in the COM settings group;
DNP 3.0 is defined as an 8 bit/no parity protocol with a 16-bit CRC
every 16 bytes. This provides better error detection than parity.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......