1MAC050144-MB C
Section 6
Supervision functions
615 series ANSI
473
Technical Manual
SCFD decision
If the self clearing fault is detected in at least one phase, the PICKUP and TRIP outputs
are set to TRUE. Also SCDetect in monitored data is set to TRUE.
When one phase detects a fault, the algorithm waits for 1 cycle time and during this period
if other two phases have detected a fault, the event is considered as three phase event and
the Event3Ph in monitored data is set to TRUE.
Activation of the BLOCK input deactivates all the binary outputs.
6.7.5
Signals
Table 403: CFD Input signals
Table 404: CFD Output signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOL
0=FALSE
Block overall function.
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......