Section 3
1MAC050144-MB C
Basic functions
64
615 series ANSI
Technical Manual
Table 40:
FR Non group settings
Table 41:
FR Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Off / On
Trig mode
0=Trip or Pickup
1=Trip only
2=Pickup only
0=Trip or Pickup
Triggering mode
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Name
Type
Values (Range)
Unit
Description
Fault number
INT32
0...999999
Fault record number
Time and date
Timestamp
Fault record time stamp
Protection
Enum
0=Unknown
Protection function
1=PHLPTOC1
2=PHLPTOC2
6=PHHPTOC1
7=PHHPTOC2
8=PHHPTOC3
9=PHHPTOC4
12=PHIPTOC1
13=PHIPTOC2
17=EFLPTOC1
18=EFLPTOC2
19=EFLPTOC3
22=EFHPTOC1
23=EFHPTOC2
24=EFHPTOC3
25=EFHPTOC4
30=EFIPTOC1
31=EFIPTOC2
32=EFIPTOC3
35=NSPTOC1
36=NSPTOC2
-7=INTRPTEF1
-5=STTPMSU1
-3=JAMPTOC1
41=PDNSPTOC1
44=T1PTTR1
46=T2PTTR1
48=MPTTR1
Table continued on next page
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......