Section 4
1MAC050144-MB C
Protection functions
174
615 series ANSI
Technical Manual
coil or the grounding resistor. This is the case for instance, when a directional ground-fault
relay is used in an MV-switching substation some kilometers from the HV/MV -substation
in which the grounding facilities are located. Another example is when
HV/MV-substations are connected in parallel but located far from each other.
It is easy to give the tripping sector such a width that all possible directions of the
I
0
-phasors of a faulty line are covered by one and the same sector. Thus, the problem of
setting the characteristic angle according to the grounding status of the network is easily
solved. There is no need to change any settings when a Petersen coil or a grounding resistor
is switched on or off. Auxiliary switches and other pieces of extra hardware are no longer
required for ensuring the selectivity of the directional ground-fault protection.
Figure 78:
Extended operation area in directional ground-fault protection
4.1.6.6
Measurement modes
The function operates on three alternative measurement modes: "RMS", "DFT" and
"Peak-to-Peak". The measurement mode is selected with the
Measurement mode
setting.
Table 161: Measurement modes supported by 67/51N and 67/50N stages
Max forward angle
RCA=0°
Current start value
Positive
operation
sector
Negative
operation
sector
-
Min forward angle
0
V
0
I
Measurement mode
Supported measurement modes
67/51N and 67/50N-1
67/50N-2
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
For a detailed description of the measurement modes, see the General
function block features section in this manual.
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......