background image

LSU 110 / 32

 

Device:  

Document: 

Code:

Date:

LSU 110 / 32

User manual LS3MUE01

15.08.2020

LSU 110 / 32

Local Signalization Unit

User manual

Summary of Contents for LSU 110/32

Page 1: ...LSU 110 32 Device Document Code Date LSU 110 32 User manual LS3MUE01 15 08 2020 LSU 110 32 Local Signalization Unit User manual ...

Page 2: ...ARY INPUTS AND OUTPUTS DESCRIPTION 8 4 SETTINGS 9 5 IEC 60870 5 103 PROTOCOL 18 5 1 INFORMATION TABLE 18 5 2 EXAMPLES OF REQUEST RESPOND SEQUENCES 19 6 SCHEMATICS 21 7 INSTALLATION 22 8 COMMISSIONING AND MAINTENANCE 24 8 1 COMMISSIONING 24 8 2 MAINTENANCE 24 9 TECHNICAL DATA 25 10 DIMENSIONS 28 11 ORDERING 29 Page Device Document Code Date 2 LSU 110 32 User manual LS3MUE01 15 08 2020 ...

Page 3: ...ou have any questions or comments related to this product please contact us on Ediseja 21 d o o Stegne 21C 1000 Ljubljana Slovenia EU Tel 00 386 51 643 411 051 643 411 Email grega flander ediseja21 com www ediseja21 com Copyright Copyright Ediseja 21 2019 All rights reserved Explanation of the symbols Read the instructions Device was tested with AC 2 5 kV voltage to check the device insulation Dev...

Page 4: ... technically qualified personnel Warning Hazardous voltage is present inside the device during operation Disregarding of safety rules can result in severe personal injury or property damage Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations Warning Device must operate completely assembled Device ...

Page 5: ...es of operation and four flashing lamp time can be set First operation mode is latched until acknowledged second mode just follow the binary input In first mode following flash lamp time can be set 0 5 s 0 75 s 1 s and 1 5 s Each DI can be delayed from 0 ms to 65 535 s Additional 4 binary inputs DIA DIB DIC DID for special purpose like remote horn and lamp acknowledge and test Function of 6 binary...

Page 6: ... one Power Error lamp illuminate green When Power Error lamp is green device is ready to operate and DO6 is activated only device without special option see ordering option 2 3 2 NORMAL OPERATION 1 example 2 example DI A lamp 1 B A DO2 1 B A DO3 1 B ack lamp 2 A DO4 1 B A DO5 1 B ack horn 3 Page Device Document Code Date 6 LSU 110 32 User manual LS3MUE01 15 08 2020 ...

Page 7: ...t B mode binary output DO2 starts to alternate from OFF to ON position and vice versa Alternation time depends on lamps flashing time setting When lamps are acknowledged button ACK LAMP pressed or input DIB activated DO2 goes to OFF position no matter of binary input states DO3 normal postion is OFF At activation of any binary input set at B mode binary output DO3 goes to ON position for 500 ms DO...

Page 8: ... of that input has equal effect as pressing button TEST DIB external acknowledge of lamps activation of that input has equal effect as pressing button ACK LAMP DIC external acknowledge of horn activation of that input has equal effect as pressing button ACK HORN DID without function Additional outputs DO1 external test active until button TEST is pressed or input DIA is active DO2 external lamp co...

Page 9: ...peed mode All lamps are flashing except first second third or fourth row column Which column is ON depends on current setting Column which is ON marks the speed of lamp is flashing first column ON flashing on 0 5 s second column ON flashing on 0 75 s third column ON flashing on 1 s fourth column ON flashing on 1 5 s Device Document Code Date Page LSU 110 32 User manual LS3MUE01 15 08 2020 9 ...

Page 10: ...t lamp logic mode Lamp logic setting lamp flashing means that when dependent input will go active lamp will flash until ACK LAMP is pressed OPERATION lamp B lamp ON means that lamp will follow the input state active inpute lamp ON non active input lamp OFF chapter OPERATION lamp A lamp OFF means lamp we are currently set lowest right Page Device Document Code Date 10 LSU 110 32 User manual LS3MUE0...

Page 11: ... to lamps by pressing button ACK HORN Single lamp logic setting is changed with button ACK LAMP When all lamps logic are set press and hold button ACK HORN for approximately 3 s Device Document Code Date Page LSU 110 32 User manual LS3MUE01 15 08 2020 11 ...

Page 12: ...t rising edge mode Rising edge setting lamp flashing means lamp we are currently set lowest right lamp ON means that lamp will be energized by high potential lamp OFF means that lamp will be energized by low potential Page Device Document Code Date 12 LSU 110 32 User manual LS3MUE01 15 08 2020 ...

Page 13: ...or 1 s Device is now in set time delay mode First left lamp is ON and it marks the lamp binary inputs to be set Last righ lamp is flashing Flashing lamp marks the setting position Set time delay for each lamp according to the pictures Device Document Code Date Page LSU 110 32 User manual LS3MUE01 15 08 2020 13 ...

Page 14: ...LSU 110 32 Local Signalization Unit User manual Move between time settings by pressing button ACK HORN Page Device Document Code Date 14 LSU 110 32 User manual LS3MUE01 15 08 2020 ...

Page 15: ...elect time setting by pressing button ACK LAMP If lamp is ON selected time delay is active If lamp is OFF selected time delay is not active Move between lamps by pressing button TEST Device Document Code Date Page LSU 110 32 User manual LS3MUE01 15 08 2020 15 ...

Page 16: ...nalization Unit User manual When time delays for all lamps are set press and hold button ACK HORN for approximately 3 s All lamps goes ON for 1 s Page Device Document Code Date 16 LSU 110 32 User manual LS3MUE01 15 08 2020 ...

Page 17: ...ing button TEST Select deselect address bit setting by pressing button ACK LAMP If lamp is ON selected bit is active If lamp is OFF selected bit is not active When IEC 60870 5 103 device address and IEC 60870 5 103 station address are set press and hold button ACK HORN for approximately 3 s All lamps goes ON for 1 s Device goes into reset After reset device is in operating mode Device Document Cod...

Page 18: ...mation table Signal description Function Information number GI respond number digital input 1 240 160 1 digital input 2 240 161 2 digital input 3 240 162 3 digital input 4 240 163 4 digital input 5 240 164 5 digital input 6 240 165 6 digital input 7 240 166 7 digital input 8 240 167 8 digital input 9 240 168 9 digital input 10 240 169 10 digital input 11 240 170 11 digital input 12 240 171 12 digi...

Page 19: ...ital output 1 200 160 NO GI digital output 2 200 161 NO GI digital output 3 200 162 NO GI digital output 4 200 164 NO GI digital output 5 200 165 NO GI digital output 6 200 166 NO GI Valid for LSU 110 32 x x x S types only For LSU 110 32 x x x N devices this output indicates device ready status 5 2 EXAMPLES OF REQUEST RESPOND SEQUENCES Device address 1 Telegrams legend master request slave respond...

Page 20: ...3 11 00 46 16 GI end 10 7A 01 7B 16 68 09 09 68 08 01 08 81 0A 01 FF 00 00 9C 16 Class 1 read 10 5A 01 5B 16 10 09 01 0A 16 10 7B 01 7C 16 10 09 01 0A 16 10 5A 01 5B 16 10 09 01 0A 16 10 7A 01 7B 16 10 09 01 0A 16 10 5B 01 5C 16 10 09 01 0A 16 DO2 68 0A 0A 68 73 01 14 81 14 01 C8 A1 02 01 8A 16 10 00 01 01 16 DO3 68 0A 0A 68 73 01 14 81 14 01 C8 A2 02 02 8C 16 10 00 01 01 16 DO4 68 0A 0A 68 73 01 ...

Page 21: ...8 2020 21 Picture 1 LSU 110 32 x x V x N x 5 schematic 4DIs in group 9 groups 5 RS485 RS232 LSU 110 32 x x V x N x N schematic 4DIs in group 9 groups N no commun port Picture 2 LSU 110 32 x x V x S x 5 schematic S separated DIs 36 groups 5 RS485 RS232 LSU 110 32 x x V x S x N schematic S separated DIs 36 groups N no commun port ...

Page 22: ...ocation must be vibration free The device is intended for mounting in 19 rack cabinet The admisible operating temperature must be observed Check the device for damage at unpacking If device is damaged it must not be installed but it should be send to the manufacturer for repair The device should not be opened Attach ground wire before attaching power supply Device must be grounded during operation...

Page 23: ...LSU 110 32 Local Signalization Unit User manual Device Document Code Date Page LSU 110 32 User manual LS3MUE01 15 08 2020 23 Picture 4 LSU 110 32 inserted papers dimensions ...

Page 24: ...must be taken into consideration Device must operate completely assembled Device must be used as described No modifications of the device should be made Attach ground wire before attaching power supply Device must be grounded during operation Check if the power supply voltage complies with device operation voltage Do not open device while it is energized Hazardous voltage is present inside the dev...

Page 25: ...ical Fuse internal 2 A T Voltage dips 20 ms Connector type screw type MSTB Phoenix 2pin Power supply wire crossection 0 5 2 5 mm2 type single or stranded wire voltage rating 500 V colour depends on used standard Ground wire crossection Cu flat 2 5 mm2 colour yellow green or natural non isolated Binary input Rated input voltage LSU 110 32 x 1 DC 24 V LSU 110 32 x 2 DC 48 V LSU 110 32 x 3 DC 110 V 1...

Page 26: ... 1 3 A at 48 V resistive bourden 0 4 A at 110 V resistive bourden 0 35 A at 220 V resistive bourden Connector type screw type MSTB Phoenix 3 pin Wire crossection 0 5 2 5 mm2 type single or stranded wire voltage rating 500 V colour depends on used standard Buzzer Sound power level 85 dB Operation Flash lamp time Programmable 0 5 s 0 75 s 1 s or 1 5 s Time to trigger DC 13 ms AC 35 ms Device Weight ...

Page 27: ...LSU 110 32 Local Signalization Unit User manual Device Class I Overvoltage category II Altitude up to 2000 m Device Document Code Date Page LSU 110 32 User manual LS3MUE01 15 08 2020 27 ...

Page 28: ...LSU 110 32 Local Signalization Unit User manual 10 DIMENSIONS Page Device Document Code Date 28 LSU 110 32 User manual LS3MUE01 15 08 2020 Picture 5 LSU 110 32 dimensions ...

Page 29: ...ur yellow Y red R green G white W mixed colour M Option 1 see chapter Schematics none without additional option 1 N separated digital inputs S Option 2 see chapter Operation none without additional option 2 N DO6 output intended for lamp acknowledge 6 Communication none N RS485 RS232 IEC 60870 5 103 protocol 5 Software Version software version leave empty Software Revision software revision leave ...

Page 30: ...ntact Ediseja 21 razvoj elektronskih naprav d o o Ediseja 21 d o o Stegne 21C 1000 Ljubljana Slovenia EU Phone 00 386 51 643 411 grega flander ediseja21 com www ediseja21 com Page Device Document Code Date 30 LSU 110 32 User manual LS3MUE01 15 08 2020 ...

Reviews: