Owner’s Manual

Reliable Emergency Backup Power

Congratulations! You’ve purchased the most advanced, feature-rich Inverter/Charger designed as an alternative energy source during utility
power failures. Tripp Lite APS Inverter/Chargers keep your equipment constantly up and productive through all utility power problems (blackouts,
brownouts and high voltages) by inverting DC power from user-supplied batteries into AC power. Built-in surge suppression provides an additional
level of equipment protection. When utility power is present, APS Inverter/Chargers automatically pass through power to your equipment while
simultaneously recharging your connected battery bank. APS Inverter/Chargers are the quiet alternative to gas generators during emergency
backup applications—with no fumes, fuel or noise to deal with! You get AC electricity anywhere and anytime you need it.

Better for Your Equipment

Premium Protection Levels

• Built-In Isobar

®

Surge Protection

• Automatic Overload Protection

Ideal Output for All Loads (including computers)

• Frequency-Controlled Output

• Fast Load Switching

• Balanced Load Sharing*

Better for Your Batteries

Faster Battery Recharge

• High-Amp, 3-Stage Battery Charger (adjustable)

Critical Battery Protection

• Battery Charge Conserver (Load Sense)*

• Battery Temperature Sensing*

• High-Efficiency DC-to-AC Inversion

Better for You

Simple, Maintenance-Free Operation

• Multi-Function Lights & Switches

• Moisture-Resistant Construction**

Specifications/Warranty

2

Safety

3

Feature Identification

4

Operation

5

Configuration

6-7

Battery Selection

8

Mounting

9

Battery Connection

10

AC Input/Output Connection

11

Service/Maintenance/Troubleshooting

12 

Español

13 

PowerVerter

®

APS Series

DC-to-AC Inverter/Chargers

Input

Output

Invert:

12, 24, 36 or 48 VDC

120V, 60 Hz. AC

Charge:

120V, 60 Hz. AC

12, 24, 36 or 48 VDC

1111 W. 35th Street, Chicago, IL 60609 USA

Customer Support: (773) 869-1234

www.tripplite.com

* Available on all models except 612, 750 and 1250 models. ** Inverter/Chargers are moisture-resistant, not waterproof. 

Copyright © 2004. PowerVerter

®

is a registered trademark of Tripp Lite. All rights reserved.

Contents

W

arranty

Registration

Register on-line toda

y f

or a c

hance

to win a FREE 

Tripp Lite pr

oduct!

www

.tripplite

.com/warranty

200407140  120V APS Owner’s Manual.qxd  9/16/2004  9:58 AM  Page 1

Содержание PowerVerter APS 1012

Страница 1: ...including computers Frequency Controlled Output Fast Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recharge High Amp 3 Stage Battery Charger adjustable Critical Batter...

Страница 2: ...APS1012 APS1250 APS1524 APS2012 APS2424 APS2448 APS3624VR APS3636VR AC Input Connection Input Cord Input Cord Input Cord Input Cord Hardwire Hardwire Hardwire Hardwire Hardwire Hardwire INVERTER Commo...

Страница 3: ...Ideally any compartment would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to c...

Страница 4: ...ing and control with an optional module Tripp Lite model APSRM4 sold separately or included with select models See remote module owner s manual for connection instructions Battery Charge Conserver Loa...

Страница 5: ...l NOT supply AC power in the absence of a utility generator source or in over under voltage situations INV Inverting Yellow Indicator This light will ILLUMINATE CONTINUOUSLYwhenever connected equipmen...

Страница 6: ...Input Point is set to 95V However if the unit frequently switches to battery power due to momentary high low line voltage swings that would have little effect on equipment operation you may wish to ad...

Страница 7: ...output at full load No Limiting B1 B2 Down No charger limiting occurs at any load size B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 Set Battery Charge Conserver Load Sense Control OPTI...

Страница 8: ...your batteries with utility or genera tor supplied AC power Compensate for inefficiency by multiplying this number by 1 2 This will give you a rough estimate of how many amp hours of battery power fr...

Страница 9: ...ger forward over the fasteners to engage the mounting feet molded on the front of the Inverter Charger cabinet Install and tighten two user supplied 6 mm fasteners into the mounting feet molded on the...

Страница 10: ...ause both positive terminals are internally bonded and both negative terminals are also internally bonded In this connection you must run one positive cable through one user supplied UL listed fuse an...

Страница 11: ...he knockouts and thread wires through Connect the conduits to each other with the ground bond connection supplied HOT IN NEUTRAL IN GROUND IN GROUND OUT HOT OUT FOR USE WITH COPPER WIRE ONLY NEUTRAL O...

Страница 12: ...TO REMOTE or CHARGE ONLY Battery Not Recharging Connected batteries are dead Check and replace old batteries AC Input Present Battery fuse is blown Check and replace fuse Battery cabling is loose Chec...

Страница 13: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...

Отзывы: