9
Scalar Control (V/f)
CFW700 | 9-11
DC Link Voltage (P0004)
F022-
Overvoltage
Time
DC Link
Regulation
Output
Speed
Time
P0151
Nominal U
d
Voltage U
d
(P0004)
Figure 9.12:
Example of the DC link voltage limitation working with the Ramp Acceleration function
P0150 – V/f DC Regulation Type
Adjustable
Range:
0 = Ramp Hold
1 = Ramp Acceleration
Factory
Setting:
0
Properties:
V/f, VVW and cfg
Access groups
via HMI:
Description:
It selects the DC link voltage limitation function type in the V/f mode.
P0151 – V/f DC Regulation Level
Adjustable
Range:
339 to 400 V
585 to 800 V
585 to 800 V
585 to 800 V
585 to 800 V
Factory
Setting:
400 V (P0296 = 0)
800 V (P0296 = 1)
800 V (P0296 = 2)
800 V (P0296 = 3)
800 V (P0296 = 4)
Properties:
V/f and VVW
Access groups
via HMI:
Description:
It is the actuation level of the DC link voltage limitation function for the V/f mode.
Setting of P0151 value:
1. The P0151 factory setting leaves inactive the DC link voltage limitation function for the V/f mode. In order to
activate it, one must reduce the value of P0151 as suggested in the
Table 9.2:
Recommended actuation levels for the DC link regulation
Inverter
V
nom
220/230 V
380 V
400/415 V
440/460 V
480 V
P0296
0
1
2
3
4
P0151
375 V
618 V
675 V
748 V
780 V
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...