18
SoftPLC
18-2 | CFW700
P1003 – SoftPLC Applicative Selection
Adjustable
Range:
0 = User
1 = PID
2 = EP
3 = Multispeed
4 = 3-Wire Start/Stop
5 = FWD Run/ REV Run
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
SPLC
Description:
It allows the user to select the CFW700 built in applications.
Table 18.1:
Parameter P1003 option description
P1003
Description
0
The application that will run in the SoftPLC is that loaded by the user via ladder programming.
1
The application that will run in the SoftPLC is the PID regulator. It can be used to control a closed loop process.
This application sets proportional, integral and derivative regulator superimposed to the regular speed control of
the CFW700 inverter.
2
The application that will run in the SoftPLC is the electronic potentiometer. It allows the motor speed reference
settings via two digital inputs, one for accelerating the motor and another to decelerate the motor.
3
The application that will run in the SoftPLC is the multispeed. It allows speed reference settings based on to
the values defined in some parameters (P1011 to P1018) with a logical combination of the digital inputs DI4, DI5
and DI6, limited to 8 pre-programmed speed references. Advantages such as stability of fixed pre-programmed
references and electrical noise immunity (isolated digital inputs DIx) are noted in this kind of application.
4
The application that will run in the SoftPLC is the 3-Wire Start/Stop. It allows the inverter to start/stop as with a
retention contact and an emergency button.
5
The application that will run in the SoftPLC is the FWD/REV command. It gives the user the combination of two
inverter commands in a single digital input (forward/reverse and start/stop).
NOTE!
Refer to SoftPLC manual for more information about the CFW700 user applications.
From P1010 to P1059 – SoftPLC Parameters
Adjustable
Range:
-32768 to 32767
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
SPLC
Description:
They consist of parameters defined by the selected application in parameter P1003.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...